Date |
Text |
2023-02-03 09:22:27 | NEW DUPLEX |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING CS-1 SAYS ASCE 7-10 - DESIGN SHOULD BE ASCE |
| 7-16 PER FBC CHAPTER 35 |
| |
| 2) PLEASE SHOW THE TYPE OF WINDOW FALL PROTECTION TO BE |
| USED - R312.2.1 WINDOW SILLS. |
| IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN |
| OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES |
| (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72 |
| INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER |
| SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE |
| OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| |
| 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A |
| 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE |
| OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED |
| POSITION. |
| |
| 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL |
| PREVENTION DEVICES THAT COMPLY WITH ASTM F2090. |
| |
| 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW |
| OPENING CONTROL DEVICES THAT COMPLY WITH SECTION |
| R312.2.2. |
| |
| 3) DRAWING A-5 SHOWS DRYWALL ATTACHED TO THE BOTTOM OF |
| THE TOP CORD OF THE TRUSSES - YOU ARE CREATING AN AIR |
| SPACE WHICH WILL NEED VENTILATION - IF USED THE DRYWALL |
| SHOULD BE ATTACHED TO THE BOTTOM OF THE ROOF SHEATHING |
| USING 2X4 BLOCKING TO HOLD IT UP SEE FBC R302.2.2 (2) |
| OR ONE LAYER OF 5/8-INCH (15.9 MM) TYPE X GYPSUM BOARD |
| IS INSTALLED DIRECTLY BENEATH THE ROOF DECKING OR |
| SHEATHING, SUPPORTED BY NOT LESS THAN NOMINAL 2-INCH |
| (51 MM) LEDGERS ATTACHED TO THE SIDES OF THE ROOF |
| FRAMING MEMBERS, FOR A DISTANCE OF NOT LESS THAN 4 FEET |
| (1219 MM) ON EACH SIDE OF THE WALL OR WALLS AND ANY |
| OPENINGS OR PENETRATIONS IN THE ROOF ARE NOT WITHIN 4 |
| FEET (1219 MM) OF THE COMMON WALLS. |
| |
| 4) PLEASE SHOW THE LOCATION AND MATERIALS USED FOR THE |
| FLOOR/CEILING DRAFT STOPPING - FBC R302.12 |
| DRAFTSTOPPING. |
| IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE |
| BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A |
| FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED |
| SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE |
| THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. |
| |
| 5) PRODUCT APPROVAL PROVIDED FOR THE EXTERIOR SWING |
| DOOR (FL17184.5) PLEASE PROVIDE THE PRODUCT APPROVAL |
| FRONT PAGES. |
| |
| 6) PRODUCT APPROVALS FOR THE GLAZED DOOR |
| (NOA18-0503.06) AND THE OVERHEAD GARAGE DOOR |
| (NOA17-1010.03) -PLEASE PROVIDE COPIES WITHOUT OTHER |
| CITY STAMPS ON THEM AND THAT ARE FOR THE 2020 FBC |
| |
| 7) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOWS AND THE |
| ROOFING SYSTEMS. |
| |
| 8) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB |
| 107.3.4 |
| |
| 9) PLEASE SHOW THAT THE FOAM INSULATION USED MEETS |
| (PROVIDE THE ICYNENE ICC EVALUATION REPORT) - FBC R316 |
| |
| 10) PLEASE SHOW THE SET BACK FOR THE SECOND FLOOR EAST |
| SIDE FROM THE PROPERTY LINE - FBC R302.1 |
| |
| 11) ALL OF THE CIVIL AND ALL OF THE STRUCTURAL DRAWINGS |
| DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - |
| SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |
| 12) FYI - SEPARATE PERMITS ARE REQUIRED FOR - SITE |
| WALL, FENCE, DRIVEWAY |