Plan Review Notes
Plan Review Notes For Permit 22090719
Permit Number 22090719
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-03 09:22:27NEW DUPLEX
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING CS-1 SAYS ASCE 7-10 - DESIGN SHOULD BE ASCE
 7-16 PER FBC CHAPTER 35
  
 2) PLEASE SHOW THE TYPE OF WINDOW FALL PROTECTION TO BE
 USED - R312.2.1 WINDOW SILLS.
 IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN
 OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES
 (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72
 INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER
 SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE
 OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING:
  
 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A
 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE
 OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED
 POSITION.
  
 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL
 PREVENTION DEVICES THAT COMPLY WITH ASTM F2090.
  
 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW
 OPENING CONTROL DEVICES THAT COMPLY WITH SECTION
 R312.2.2.
  
 3) DRAWING A-5 SHOWS DRYWALL ATTACHED TO THE BOTTOM OF
 THE TOP CORD OF THE TRUSSES - YOU ARE CREATING AN AIR
 SPACE WHICH WILL NEED VENTILATION - IF USED THE DRYWALL
 SHOULD BE ATTACHED TO THE BOTTOM OF THE ROOF SHEATHING
 USING 2X4 BLOCKING TO HOLD IT UP SEE FBC R302.2.2 (2)
 OR ONE LAYER OF 5/8-INCH (15.9 MM) TYPE X GYPSUM BOARD
 IS INSTALLED DIRECTLY BENEATH THE ROOF DECKING OR
 SHEATHING, SUPPORTED BY NOT LESS THAN NOMINAL 2-INCH
 (51 MM) LEDGERS ATTACHED TO THE SIDES OF THE ROOF
 FRAMING MEMBERS, FOR A DISTANCE OF NOT LESS THAN 4 FEET
 (1219 MM) ON EACH SIDE OF THE WALL OR WALLS AND ANY
 OPENINGS OR PENETRATIONS IN THE ROOF ARE NOT WITHIN 4
 FEET (1219 MM) OF THE COMMON WALLS.
  
 4) PLEASE SHOW THE LOCATION AND MATERIALS USED FOR THE
 FLOOR/CEILING DRAFT STOPPING - FBC R302.12
 DRAFTSTOPPING.
 IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
  
 5) PRODUCT APPROVAL PROVIDED FOR THE EXTERIOR SWING
 DOOR (FL17184.5) PLEASE PROVIDE THE PRODUCT APPROVAL
 FRONT PAGES.
  
 6) PRODUCT APPROVALS FOR THE GLAZED DOOR
 (NOA18-0503.06) AND THE OVERHEAD GARAGE DOOR
 (NOA17-1010.03) -PLEASE PROVIDE COPIES WITHOUT OTHER
 CITY STAMPS ON THEM AND THAT ARE FOR THE 2020 FBC
  
 7) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOWS AND THE
 ROOFING SYSTEMS.
  
 8) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 9) PLEASE SHOW THAT THE FOAM INSULATION USED MEETS
 (PROVIDE THE ICYNENE ICC EVALUATION REPORT) - FBC R316
  
 10) PLEASE SHOW THE SET BACK FOR THE SECOND FLOOR EAST
 SIDE FROM THE PROPERTY LINE - FBC R302.1
  
 11) ALL OF THE CIVIL AND ALL OF THE STRUCTURAL DRAWINGS
 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 12) FYI - SEPARATE PERMITS ARE REQUIRED FOR - SITE
 WALL, FENCE, DRIVEWAY