2023-01-05 12:46:47ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS NOT ADDRESSED, SEE PREVIOUS
 COMMENTS
  
 PLEASE DETAIL SIZING CALCULATIONS FOR HANDHOLE.
  
 PLEASE INDICATE HOW THE EMERGENCY SYSTEM WILL BE KEPT
 COMPLETELY INDEPENDENT OF ALL OTHER WIRING AS PER NEC
 700.10 (B)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  