2022-09-21 09:38:25 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10124-R31 |
| HAS BEEN REVISED TO FL10124-R32. PLEASE PROVIDE A |
| COMPLETE SET; IT COVERS MULTIPLE PRODUCTS & |
| INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION |
| METHOD TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. |
| 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL17084-R10 IS NOT APPROVED FOR USE AS A SEAM |
| TAPE. PROVIDE A COMPLETE SET OF 2020 CODE VERSION |
| PRODUCT APPROVALS/NOA'S FOR THE PROPOSED ROOF |
| UNDERLAYMENT (JOINT TAPE/STRIPS) TO BE USED. INCLUDE |
| COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. OPTION FL12328-R9 (NON-HVHZ) |
| 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16717-R12 |
| (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| CONSIDER USING FL1654-R29 (NON-HVHZ). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |