Plan Review Notes For Permit 22090623 |
Permit Number |
22090623 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-10-20 08:31:33 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL2533-R28 SYSTEM NO. W-105 DO NOT MEET THE | | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -131.42 | | FOR EXPOSURE CATEGORY D AREAS. PROVIDE SYSTEM THAT | | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR | | EXPOSURE CATEGORY D/PROVIDE SIGNED AND SEALED | | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED | | SYSTEM. | | 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF | | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW | | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|