2023-03-08 10:48:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW LOAD CALCULATION PROVIDED. NEC PART IV
 OPTIONAL FEEDER AND SERVICE LOAD CALCULATIONS 220.82
 (A)(B)(C)
  
 2. PANEL SCHEDULE PROVIDED IS NOT IN ACCORDANCE WITH
 ELECTRICAL PLAN PROVIDED. NEC 408.4(A).
  
 3. PROVIDE INFORMATION OF EXISTING SERVICE (FOR
 EXAMPLE: SERVICE CONDUCTORS AND PROTECTION). FBC
 107.3.5.3
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  