Notes |
Date |
Text |
2023-03-08 10:48:03 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. REVIEW LOAD CALCULATION PROVIDED. NEC PART IV | | OPTIONAL FEEDER AND SERVICE LOAD CALCULATIONS 220.82 | | (A)(B)(C) | | | | 2. PANEL SCHEDULE PROVIDED IS NOT IN ACCORDANCE WITH | | ELECTRICAL PLAN PROVIDED. NEC 408.4(A). | | | | 3. PROVIDE INFORMATION OF EXISTING SERVICE (FOR | | EXAMPLE: SERVICE CONDUCTORS AND PROTECTION). FBC | | 107.3.5.3 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] |
|