Plan Review Notes
Plan Review Notes For Permit 22090533
Permit Number 22090533
Review Stop B
Sequence Number 2
Notes
Date Text
2022-12-08 19:00:47RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22090533
 3650 WHITEHALL DR #404
  
 ORIGINAL COMMENT:
 1- WINDOW MULLIONS:
 A)1X3 MULLIONS DON'T MEET THE CALCULATED DESIGN
 PRESSURES FOR ALL OPENINGS. REVISE AS REQUIRED. SEC.
 1609.1 FBC-BUILDING.
  
 RESPONSE:
 NEW MULLION NOA 19-0405.10 SUBMITTED:
 SAME COMMENT APPLIES. 1X3 MULLIONS AND 2X3 MULLIONS
 DON'T MEET THE CALCULATED DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 B)CLEARLY MARK ON THE PRODUCT APPROVAL MULLION
 FASTENING. SEC. 1609.1 FBC-BUILDING.
  
 RESPONSE:
 MULLION PRODUCT APPROVAL WAS NOT MARKED SHOWING
 FASTENING.
  
 ORIGINAL COMMENT:
 C) CLARIFY SIZE OF CORNER MULLION. FLOOR PLAN SUBMITTED
 SPECIFIES 3X3 MULLION, WHILE MULLION PRODUCT APPROVAL
 IS MARKED WITH A 4X4 MULLION. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NEW MULLION NOA 19-0405.10 SUBMITTED:
 2X3 MULLIONS DON'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 ORIGINAL COMMENT:
 D)MULLION FLORIDA PRODUCT APPROVAL FL34545 STATES IN
 ALL SHEETS THAT "THESE MULLIONS CAN ONLY BE USED WITH
 'MARVIN' GLAZING PRODUCTS". NEED TO PROVIDE GLAZING
 PRODUCTS TO USE WITH THESE MULLIONS OR PROVIDE ANOTHER
 MULLION PRODUCT APPROVAL.
 FAC 61G20.3.001.
  
 RESPONSE:
 NEW MULLION NOA 19-0405.10 SUBMITTED. THIS ONE IS OK,
 BUT SIZE OF MULLIONS SPECIFIED ON THE FLOOR PLAN
 DON???T MEET THE CALCULATED DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 2- WINDOW OPENING CONTROL DEVICES: WINDOW OPENING
 CONTROL DEVICES ARE REQUIRED WHEN THE WINDOW SILL OF AN
 OPERABLE WINDOW IS AT A HEIGHT LESS THAN 36 INCHES
 ABOVE THE FINISHED FLOOR.
 WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM
 F2090.
 CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE
 WINDOW SILL IS LESS THAN 36" ABOVE THE FINISH FLOOR.
 SEE SEC. 702.4 FBC-EXISTING BUILDING CODE.
  
 RESPONSE:
 THIS WILL BE VERIFIED IN THE FIELD BY THE BUILDING
 INSPECTOR. THIS COMMENT IS JUST TO GIVE HEADS UP ABOUT
 THIS REQUIREMENT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712