| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE |
| REPORT PREPARED BY A FLORIDA REGISTERED DESIGN |
| PROFESSIONAL. |
| 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY |
| LIMITATIONS 5.6.3 OF PRODUCT APPROVAL FL2948-R16. |
| 3. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). |
| 5. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART |
| OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS |
| BY YOUR BUILDING INSPECTOR. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |