2022-09-20 08:26:20 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND |
| SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR |
| PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL |
| LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 21-1207.12 SYSTEM |
| TYPE E (1). PLEASE NOTE THIS PROJECT IS LOCATED IN AN |
| EXPOSURE C CATEGORY AREA. |
| 2. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| INDICATE ON ROOF DRAWING/SKETCH). |
| 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |