2022-10-28 07:48:56 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22090368 |
| 10/28/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET E-1: THE KITCHENETTE SINK DRAIN SHALL |
| DISCHARGE DOWNSTREAM OF THE BATHROOM HORIZONTAL OR |
| VERTICAL WET VENT, AND SHALL BE SEPARATELY VENTED PER |
| SECS. 912.1 & 912.1.1 FBC P. |
| |
| 2) E-1: THE VENT SYSTEM SERVING EACH BUILDING DRAIN |
| SHALL HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO |
| THE OUTDOORS- SEC. 904.1 FBC P. |
| |
| 3) A-2 & E-1: SHOW THE LOCATIONS OF THE REQUIRED |
| SERVICE SINK AND DRINKING FOUNTAINS FOR THE OCCUPANCY- |
| SEE TABLE 403.1 & SEC. 410.3 FBC P- A MINIMUM OF TWO |
| DRINKING FOUNTAINS SHALL BE PROVIDED- ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| |
| 4) E-1: REVISE THE SANITARY ISOMETRIC TO THE SHOW THE |
| DRAINAGE AND VENT SYSTEMS FOR THE ADDITIONAL REQUIRED |
| FIXTURES, AND PROVIDE A WATER RISER THAT AND THE HOT |
| AND COLD WATER SUPPLY PIPES TO THE FIXTURES AND THE |
| SOURCE OF THE HOT WATER- SEC. 107.3.5.1.3 WPB AND SEC. |
| 607.1 FBC P. CLARIFY IF THERE IS AN EXISTING WATER |
| HEATER IN THE SPACE OR IF A NEW UNIT WILL BE INSTALLED. |
| |
| A) TEMPERATURE LIMITING MEANS ??? PLEASE NOTE THE |
| THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE |
| LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE |
| A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| WATER DELIVERY- SEC. 607.1.1 FBC P. |
| |
| B) PLEASE NOTE THAT IF HOT WATER IS SUPPLIED TO THE |
| LAVATORY THE WATER SHALL BE TEMPERED PER SEC. 419.5 FBC |
| P. A TEMPERATURE LIMITING DEVICE CONFORMING TO ASSE |
| 1070 SHALL BE PROVIDED- SEC. 607.1.2 FBC P. |
| |
| C) PROVIDE HOT WATER PIPING INSULATION DETAILS- TABLE |
| C403. |
| |
| 5) A-2 & E-1: PROVIDE THE FOLLOWING DETAILS FOR THE |
| BATHROOM AND KITCHEN FIXTURES ON THE PLAN IN COMPLIANCE |
| WITH THE FBC ACC. |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORY AND KITCHEN SINKS- SECTION 606.2. |
| C) TURNING SPACE DIAMETER- SECTION 304.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| F) HEIGHTS OF THE LAVATORY AND KITCHEN SINK RIMS OR |
| COUNTER SURFACE FROM THE FINISHED FLOOR- SECTION 606.3. |
| G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| REFLECTIVE SURFACE- SECTION 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| FIGURES 604. |
| I) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| 604.6. |
| J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONTS OF THE WATER CLOSET- SECTION AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORY AND KITCHEN |
| SINK- SECTION 606.2. PLEASE NOTE A PARALLEL APPROACH IS |
| ACCEPTABLE FOR THE KITCHEN SINK. |
| L) DRINKING FOUNTAINS- REFER TO SECTIONS 306, 307, AND |
| 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION |
| 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE |
| FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| PROTRUSION LIMITS. |
| |
| 6) A-2: PROVIDE A SLAB REPAIR AND SOIL TREATMENT |
| DETAIL- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |