Plan Review Notes
Plan Review Notes For Permit 22090268
Permit Number 22090268
Review Stop B
Sequence Number 1
Notes
Date Text
2022-09-19 11:14:01JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOFING TILE SYSTEM TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING
 2.FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED. (FL5374-R6)
 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE TILE ADHESIVE TO BE USED.
 4. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 17-1003.15 SYSTEM TYPE A (1) MAXIMUM DESIGN PRESSURE
 -45 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C AREAS.
 GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. THE MAXIMUM DESIGNED PRESSURE LIMITATION
 LISTED SHALL BE APPLICABLE TO ALL ROOF PRESSURE ZONES
 (I.E. FIELD, PERIMETERS, AND CORNERS). NEITHER RATIONAL
 ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR
 ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E.
 PERIMETERS, EXTENDED CORNERS AND CORNERS). THIS SYSTEM
 CAN???T BE USED. PROVIDE SYSTEM THAT MEETS OR EXCEEDS
 THESE REQUIREMENTS.
 5. FBC B 107.2.1 1 PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: AERIAL MAP OF THE ENTIRE COMPLEX WITH EACH
 BUILDING CLEARLY IDENTIFIED BY NUMBER; EACH PERMIT
 APPLICATION SHOULD ALSO REFLECT THE BUILDING NUMBER TO
 BE REROOFED.
 6. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART
 OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS
 BY YOUR BUILDING INSPECTOR.
 7. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  