2022-09-19 11:14:01 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOFING TILE SYSTEM TO |
| BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING |
| 2.FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. (FL5374-R6) |
| 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE TILE ADHESIVE TO BE USED. |
| 4. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| 17-1003.15 SYSTEM TYPE A (1) MAXIMUM DESIGN PRESSURE |
| -45 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE |
| REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C AREAS. |
| GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED TO IN |
| THIS NOA. THE MAXIMUM DESIGNED PRESSURE LIMITATION |
| LISTED SHALL BE APPLICABLE TO ALL ROOF PRESSURE ZONES |
| (I.E. FIELD, PERIMETERS, AND CORNERS). NEITHER RATIONAL |
| ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR |
| ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E. |
| PERIMETERS, EXTENDED CORNERS AND CORNERS). THIS SYSTEM |
| CAN???T BE USED. PROVIDE SYSTEM THAT MEETS OR EXCEEDS |
| THESE REQUIREMENTS. |
| 5. FBC B 107.2.1 1 PROVIDE THE FOLLOWING ADDITIONAL |
| INFORMATION: AERIAL MAP OF THE ENTIRE COMPLEX WITH EACH |
| BUILDING CLEARLY IDENTIFIED BY NUMBER; EACH PERMIT |
| APPLICATION SHOULD ALSO REFLECT THE BUILDING NUMBER TO |
| BE REROOFED. |
| 6. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART |
| OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS |
| BY YOUR BUILDING INSPECTOR. |
| 7. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| WALL CONNECTIONS WILL BE IMPROVED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |