2022-10-05 06:16:591ST REVIEW FMC
 PERMIT: 22090260
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) OUR RECORDS INDICATE THERE HAS BEEN NO PERMITTED
 MECHANICAL SYSTEM INSTALLED AT THIS ADDRESS. PLEASE
 SUBMIT THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR
 THIS PROJECT.
  
 2) PROVIDE THE ENERGY CALCULATIONS. FBC 107.3.5
  
 3) THE DRYER DUCT MUST MEET THE MATERIAL REQUIREMENTS
 OF FMC M1502.4.1
  
 M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A
 SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL
 HAVING A MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE).
 THE DUCT SHALL BE 4 INCHES (102 MM) NOMINAL IN
 DIAMETER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  