2022-09-16 11:19:43 | 1ST PLUMBING REVIEW | | 22090133 | | 9/16/22 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 3 & 6: PLEASE PROVIDE TDH CALCULATIONS- SEC. | | 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7. | | | | 2) SHEET 3 & 6: PROVIDE THE JANDY 2.7 HP PUMP CURVE ON | | THE SHEET MARKED UP TO SHOW THE TDH AND FLOW RATES OF | | THE SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & | | R4501.7.2 & R4501.7.3 FBC RES. PLEASE CORRECT THE PLAN | | NOTES INDICATING A 3HP PUMP PER THE SUBMITTED PUMP | | SPECS. | | | | 3) SHEET 3: PROVIDE POOL EQUIPMENT MOUNTING PAD AND | | EQUIPMENT ANCHORING DETAILS- SEC. R4501.22 FBC RES. | | | | 4) SHEET 1: PLEASE NOTE THE POOL IS BEING CONSTRUCTED | | IN AN AE FLOOD HAZARD ZONE. PLEASE PROVIDE EQUIPMENT | | PAD ELEVATION SHEET 3 & 6: PLEASE PROVIDE TDH | | CALCULATIONS- SEC. 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7. | | | | 5) SHEET 3: PLEASE NOTE THAT THE GAS HEATER SHALL BE | | INSTALLED UNDER A SEPARATE PERMIT- SECS. 105.1, | | 107.2.1, 107.3.5.3 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPER L. COLE | | 561-805-6719 | | [email protected] | | | | | | | | | | |
|