2022-09-16 11:19:431ST PLUMBING REVIEW
 22090133
 9/16/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3 & 6: PLEASE PROVIDE TDH CALCULATIONS- SEC.
 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7.
  
 2) SHEET 3 & 6: PROVIDE THE JANDY 2.7 HP PUMP CURVE ON
 THE SHEET MARKED UP TO SHOW THE TDH AND FLOW RATES OF
 THE SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES. PLEASE CORRECT THE PLAN
 NOTES INDICATING A 3HP PUMP PER THE SUBMITTED PUMP
 SPECS.
  
 3) SHEET 3: PROVIDE POOL EQUIPMENT MOUNTING PAD AND
 EQUIPMENT ANCHORING DETAILS- SEC. R4501.22 FBC RES.
  
 4) SHEET 1: PLEASE NOTE THE POOL IS BEING CONSTRUCTED
 IN AN AE FLOOD HAZARD ZONE. PLEASE PROVIDE EQUIPMENT
 PAD ELEVATION SHEET 3 & 6: PLEASE PROVIDE TDH
 CALCULATIONS- SEC. 4.4.9 & 4.4.9.1 ANSI/APSP/1CC-7.
  
 5) SHEET 3: PLEASE NOTE THAT THE GAS HEATER SHALL BE
 INSTALLED UNDER A SEPARATE PERMIT- SECS. 105.1,
 107.2.1, 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  