2022-10-14 14:10:33 | 1ST PLUMBING REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE |
| THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE |
| LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE |
| A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE |
| REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| 607.1.2/419.5. AND, THE DEVICE SHALL MEET THE ASSE 1017 |
| STANDARD AND BE INSTALLED AT THE HOT WATER SOURCE PER |
| 613.1. |
| |
| 2. 2020 FPC 403.1.1 FIXTURE CALCULATIONS - WITH AN |
| OCCUPANT LOAD OF 72 IN BUSINESS (1 PER 25), YOU NEED TO |
| BATHROOMS FOR EACH SEX. YOU ALSO NEED ONE ADA BATHROOM |
| PER. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |