2022-10-14 14:10:331ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL MEET THE ASSE 1017
 STANDARD AND BE INSTALLED AT THE HOT WATER SOURCE PER
 613.1.
  
 2. 2020 FPC 403.1.1 FIXTURE CALCULATIONS - WITH AN
 OCCUPANT LOAD OF 72 IN BUSINESS (1 PER 25), YOU NEED TO
 BATHROOMS FOR EACH SEX. YOU ALSO NEED ONE ADA BATHROOM
 PER.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  