Plan Review Notes
Plan Review Notes For Permit 22090123
Permit Number 22090123
Review Stop M
Sequence Number 1
Notes
Date Text
2022-10-19 09:04:141ST REVIEW FMC
 PERMIT: 22090123
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE RETURN AIR PATH FOR EACH UNIT. I
 UNDERSTAND THIS IS AN ABOVE THE CEILING RETURN PLENUM.
 PLEASE SHOW HOW THE RETURN AIR WILL BE ABLE TO MAKE IT
 INTO THIS PLENUM IN THE ENTIRE TENANT SPACE.
  
 2) PLEASE EXPLAIN, WHAT IS THE IMMERSION ROOM AND WHAT
 IS IT???S USE?
  
 3) REVISE DRAWING TO SHOW THE REQUIRED SMOKE DETECTORS
 IN THE SUPPLY SIDE OF THE DUCTWORK AT EACH MECHANICAL
 UNIT. FMC 607.5
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE. USE THE OCCUPANCY CLASSIFICATION THAT MOST
 CLOSELY ALIGNS WITH THE USE OF SPACE FROM FMC TABLE
 403.3.1.1. FMC 403.3.1.1
  
 5) SHOW THE ACCESS FOR EACH OF THE MECHANICAL UNITS
 THAT WILL BE ABOVE THE CEILING. FMC 306.1
  
 6) PROVIDE A SCALE FOR THE MECHANICAL DRAWINGS. I HAVE
 NO WAY OF CHECKING THE DISTANCE OF EXHAUST TERMINATION
 LOCATIONS TO OPENINGS INTO THE BUILDING. FMC 501.3.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  