Date |
Text |
2022-11-03 14:52:35 | REMODEL - ADDITION ?? |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) BUILDING PERMIT APPLICATION SAYS "INTERIOR |
| RENOVATION" YET THE PLANS PROVIDED SHOW AN ADDITION - |
| PLEASE CORRECT THE BUILDING PERMIT APPLICATION "WORK |
| DESCRIPTION" OR REMOVE THE ADDITION DRAWINGS FROM |
| PROJECTDOX. |
| CANNOT APPROVE AN INTERIOR RENOVATION FOR A |
| NON-EXISTENT BUILDING - THE ADDITION IS SHOWN ON THE |
| INTERIOR FLOOR PLAN. |
| |
| 2) MOST OF THE DRAWINGS PROVIDED HAVE THE STATEMENT |
| "NOT FOR CONSTRUCTION" CANNOT APPROVE DRAWINGS WITH |
| THAT NOTE ON THEM - PLEASE REMOVE THE NOTE. |
| |
| 3) DRAWINGS SHOW ACCESSIBLE PARKING TO BE REMOVED - |
| PLEASE SHOW NEW ACCESSIBLE PARKING, ACCESS AISLE AND |
| ACCESSIBLE PATH TO THE ENTRY FBC A |
| |
| 4) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING |
| INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION |
| DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| WATER RETAINING SWALES) |
| |
| 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE ROOFING SYSTEM. FBC WPB |
| 107.2.1.1 |
| |
| 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE TOILET |
| AND MOP SINK TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| CONSIDERED A HARD SURFACE) |
| |
| 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER |
| HOLDER DIMENSIONS FROM THE FACE OF THE TOILET PER FBC A |
| 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS |
| |
| 8) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| "REFLECTING SURFACE" WHEN REFERRING TO THE DIMENSION |
| FROM THE FLOOR TO THE BOTTOM OF THE MIRROR FBC A 603.3 |
| MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 9) ACCESSIBLE RESTROOM = PLEASE SHOW THE MAXIMUM HEIGHT |
| OF THE TOILET OR SHOWER GRAB BAR TO THE TOP OF THE |
| GRIPPING SURFACE NOT TO THE CENTER AS SHOWN ON THE |
| DRAWING (A-003) - FBC A 609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, |
| |
| 10) DRAWING A-300 - ACCESSIBLE DETAILS SHOULD BE PER |
| 2020 FBC ACCESSIBILITY |
| |
| 11) PLEASE SHOW THE NEW EXTERIOR DOOR LANDINGS - FBC |
| 1010.1.5 |
| |
| 12) PLEASE SHOW THE NEW FLOOR SLAB THICKNESS - FBC |
| 1907.1 |
| |
| 13) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED - |
| FBC 1816 |
| |
| |
| |