Plan Review Notes
Plan Review Notes For Permit 22090123
Permit Number 22090123
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-03 14:52:35REMODEL - ADDITION ??
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING PERMIT APPLICATION SAYS "INTERIOR
 RENOVATION" YET THE PLANS PROVIDED SHOW AN ADDITION -
 PLEASE CORRECT THE BUILDING PERMIT APPLICATION "WORK
 DESCRIPTION" OR REMOVE THE ADDITION DRAWINGS FROM
 PROJECTDOX.
 CANNOT APPROVE AN INTERIOR RENOVATION FOR A
 NON-EXISTENT BUILDING - THE ADDITION IS SHOWN ON THE
 INTERIOR FLOOR PLAN.
  
 2) MOST OF THE DRAWINGS PROVIDED HAVE THE STATEMENT
 "NOT FOR CONSTRUCTION" CANNOT APPROVE DRAWINGS WITH
 THAT NOTE ON THEM - PLEASE REMOVE THE NOTE.
  
 3) DRAWINGS SHOW ACCESSIBLE PARKING TO BE REMOVED -
 PLEASE SHOW NEW ACCESSIBLE PARKING, ACCESS AISLE AND
 ACCESSIBLE PATH TO THE ENTRY FBC A
  
 4) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM. FBC WPB
 107.2.1.1
  
 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE TOILET
 AND MOP SINK TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 HOLDER DIMENSIONS FROM THE FACE OF THE TOILET PER FBC A
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
 8) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTING SURFACE" WHEN REFERRING TO THE DIMENSION
 FROM THE FLOOR TO THE BOTTOM OF THE MIRROR FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 9) ACCESSIBLE RESTROOM = PLEASE SHOW THE MAXIMUM HEIGHT
 OF THE TOILET OR SHOWER GRAB BAR TO THE TOP OF THE
 GRIPPING SURFACE NOT TO THE CENTER AS SHOWN ON THE
 DRAWING (A-003) - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 10) DRAWING A-300 - ACCESSIBLE DETAILS SHOULD BE PER
 2020 FBC ACCESSIBILITY
  
 11) PLEASE SHOW THE NEW EXTERIOR DOOR LANDINGS - FBC
 1010.1.5
  
 12) PLEASE SHOW THE NEW FLOOR SLAB THICKNESS - FBC
 1907.1
  
 13) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED -
 FBC 1816
  
  
  