2022-09-19 07:50:41 | 1ST REVIEW PLUMBING- 2020 | | 9/19/22 | | PERMIT- 22090098 | | | | CODES IN EFFECT | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WILKINS 975XL RPZ | | DOES NOT SHOW THAT THE DEVICE MEETS THE REQUIREMENTS OF | | NSF/ANSI/CAN 61 (0.25% MAX WEIGHTED AVERAGE LEAD | | CONTENT). SUBMIT SPECS FOR THE 975XL2 WHICH MEETS THE | | REQUIREMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|