2023-01-12 09:45:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22081426
 1/12/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING IN COMPLIANCE WITH SEC.
 107.3.5.1.3 WPB. THE RISER SHALL INCLUDE THE FOLLOWING
 INFORMATION AS REQUIRED BY SEC. 402 FBC FG.
  
 A) TYPE OF GAS- NATURAL OR LP. (PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED FOR LP TANKS).
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD OF THE GENERATOR AND ALL EXISTING
 APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SHOW THE TYPE AND SIZE OF CONNECTOR FROM THE
 SHUTOFF/REGULATOR ASSEMBLY TO THE GENERATOR. PLEASE
 NOTE THE GENERATOR SHALL NOT BE RIGIDLY CONNECTED TO
 THE GAS SUPPLY- SECS. 411.1.5 & 616.2 FBC FG.
 A) PLEASE NOTE THE SUBMITTED MANUFACTURER' S
 SPECIFICATIONS FOR THE GENERATOR RECOMMENDS THE
 REGULATOR TO BE LOCATED A MINIMUM 10 FT. FROM THE
 GENERATOR SET CONNECTION POINT- SEE PAGE 2 OF THE
 GENERAC DESIGN GUIDE WHICH ALSO PROVIDES REGULATOR
 SELECTION SPECIFICATIONS- SEC. 410.2 FBC FG.
  
 3) PROVIDE A DIMENSIONED SITE PLAN WITH ENLARGED
 DRAWING OF THE GENERATOR SHOWING THE FOLLOWING
 INFORMATION.
 A) GAS PIPING RUNS ON THE EXTERIOR AND INTERIOR THE
 BUILDING AND MEANS OF PROTECTING PIPING FROM PHYSICAL
 DAMAGE AND CORROSION- SEC. 404.
 B) PROTECTION FROM VEHICLE IMPACT FOR THE GENERATOR AND
 APPURTENANCES- SEC. 303.4.
  
 4) PROVIDE A VENTING PLAN FOR THE GENERATOR EXHAUST
 LISTING THE CATEGORY OF THE VENT SYSTEM- 1,2,3, OR 4,
 AND VENT SPECIFICARTIONS- TYPES ANSD SIZE, VENT RUN AND
 TERNINATION LOCATION WITH CLEARANCE DISTANCES TO
 MECHANICAL AND GRAVITY AIR INTALES INTO THE BUILDING-
 SEC. 503.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  