2023-01-12 09:45:15 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 22081426 |
| 1/12/23 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A GAS RISER DRAWING IN COMPLIANCE WITH SEC. |
| 107.3.5.1.3 WPB. THE RISER SHALL INCLUDE THE FOLLOWING |
| INFORMATION AS REQUIRED BY SEC. 402 FBC FG. |
| |
| A) TYPE OF GAS- NATURAL OR LP. (PLEASE NOTE SEPARATE |
| PERMITS ARE REQUIRED FOR LP TANKS). |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD OF THE GENERATOR AND ALL EXISTING |
| APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) SHOW THE TYPE AND SIZE OF CONNECTOR FROM THE |
| SHUTOFF/REGULATOR ASSEMBLY TO THE GENERATOR. PLEASE |
| NOTE THE GENERATOR SHALL NOT BE RIGIDLY CONNECTED TO |
| THE GAS SUPPLY- SECS. 411.1.5 & 616.2 FBC FG. |
| A) PLEASE NOTE THE SUBMITTED MANUFACTURER' S |
| SPECIFICATIONS FOR THE GENERATOR RECOMMENDS THE |
| REGULATOR TO BE LOCATED A MINIMUM 10 FT. FROM THE |
| GENERATOR SET CONNECTION POINT- SEE PAGE 2 OF THE |
| GENERAC DESIGN GUIDE WHICH ALSO PROVIDES REGULATOR |
| SELECTION SPECIFICATIONS- SEC. 410.2 FBC FG. |
| |
| 3) PROVIDE A DIMENSIONED SITE PLAN WITH ENLARGED |
| DRAWING OF THE GENERATOR SHOWING THE FOLLOWING |
| INFORMATION. |
| A) GAS PIPING RUNS ON THE EXTERIOR AND INTERIOR THE |
| BUILDING AND MEANS OF PROTECTING PIPING FROM PHYSICAL |
| DAMAGE AND CORROSION- SEC. 404. |
| B) PROTECTION FROM VEHICLE IMPACT FOR THE GENERATOR AND |
| APPURTENANCES- SEC. 303.4. |
| |
| 4) PROVIDE A VENTING PLAN FOR THE GENERATOR EXHAUST |
| LISTING THE CATEGORY OF THE VENT SYSTEM- 1,2,3, OR 4, |
| AND VENT SPECIFICARTIONS- TYPES ANSD SIZE, VENT RUN AND |
| TERNINATION LOCATION WITH CLEARANCE DISTANCES TO |
| MECHANICAL AND GRAVITY AIR INTALES INTO THE BUILDING- |
| SEC. 503.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |