2023-03-16 16:56:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE DETAILS FOR THE GENERATOR PAD AND SPECIFY
 HOW THE GENERATOR WILL BE ANCHORED TO THE PAD TO RESIST
 WIND LOADS. FBC 107.2.1 AND CHAPTER 16
  
 2) SPECIFY THE WIND LOAD DESIGN DATA ON THE DRAWINGS.
 FBC CHAPTER 16
  
 3) DRAWINGS AND DETAILS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. FS471