Plan Review Notes
Plan Review Notes For Permit 22081417
Permit Number 22081417
Review Stop E
Sequence Number 1
Notes
Date Text
2022-10-13 15:30:32ELECTRICAL REVIEW FAILED
 1) PLEASE PROVIDE A TEMPORARY ELECTRICAL SERVICE RISER
 AND ELECTRIC LOAD CALCULATION FOR ENTIRE SEVICE,
 INCLUDE ALL TRAILERS AND
 OTHER ELECTRIC LOADS. NEC 215.5
 2) PROVIDE A SITE PLAN SHOWING LOCATION OF TEMPORARY
 SERVICE. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved