Plan Review Notes
Plan Review Notes For Permit 22081397
Permit Number 22081397
Review Stop B
Sequence Number 4
Notes
Date Text
2022-10-12 08:36:324TH NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, CBO, BU, BN, PX, CFM
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
 FEMA TECH BULLETIN #1
  
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION A9 (C) STATES "TOTAL NET AREA OF FLOOD
 OPENINGS IS 2000 SQ. IN."
 NOTE: (IF FLOOD VENT MODEL 1540-520 IS 8.25"X16.25",
 THEN EACH VENT CAN ONLY BE 134 SQ. IN.'S FOR A MAX OF
 1340 SQ. IN.'S.)
  
 NET AREA OF ENGINEERED FLOOD VENTS SHALL BE CALCULATED
 BY A DESIGN PROFESSIONAL PER FEMA TECH. BULLETIN #1,
 PAGE 34, FIGURE 25.
  
 2. COMMENT IN SECTION D STATES "SMART VENT MODEL
 1540-520 ARE RATED FOR 200 SQ. IN. PER UNIT". (THIS
 SHOULD STATE 200 SQ. FT. PER UNIT). PLEASE CORRECT.
  
 3. COMMENT IN SECTION D STATES SECTION C2E: A/C PAD AT
 SOUTHSIDE=8.96.
 EQUIPMENT SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DESIGN FLOOD ELEVATION (DFE) OF 9'0"NAVD. PLEASE
 CORRECT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  