Plan Review Notes For Permit 22081397 |
Permit Number |
22081397 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-09-21 14:03:54 | ELEVATION CERTIFICATE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | PER FEMA ELEVATION INSTRUCTIONS | | | | CORRECTIONS NEEDED - | | | | 1) A9(A) = SHOULD SHOW 1801 SQ. FT. - SEE APPROVED PLAN | | | | 2) A9(B) = SHOULD SHOW 10 - SEE APPROVED PLAN | | | | 3) A9(C) = SHOULD SHOW 2000 SQ. FT - SEE APPROVED PLAN | | | | 4) SECTION "D" - FOR THE GARAGE THE INCORRECT SQUARE | | FOOTAGE AND THE INCORRECT NUMBER OF FLOOD VENTS ARE | | NOTED - SEE APPROVED PLANS. | | | | 5) PHOTOS - PLEASE PROVIDE 2 ADDITIONAL PHOTOS - FOR A | | 2 STORY BUILDING A PHOTO LABELED "RIGHT SIDE VIEW" AND | | A PHOTO LABELED "LEFT SIDE VIEW" ARE REQUIRED. | | | | 6) THE PROVIDED SURVEY SHOWS FLOOD ELEVATION AE 6 - | | SHOULD SHOW AE 6 AND 7. | | | | | | | | | | | | | | | | | | | | | | | | |
|