Plan Review Notes
Plan Review Notes For Permit 22081397
Permit Number 22081397
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-30 09:46:08ELEVATION CERTIFICATE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 PER FEMA ELEVATION INSTRUCTIONS
  
 CORRECTIONS NEEDED -
  
 1) A9(C) = WHEN THE FLOOD VENTS ARE ENGINEERED OPENINGS
 A STATEMENT IS REQUIRED FROM THE DESIGNER OF RECORD -
 FBC R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD
 ELEVATION. (2.1) THE TOTAL NET AREA OF NON-ENGINEERED
 OPENINGS SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2)
 FOR EACH SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE
 THE ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE
 ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS
 ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN
 PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL
 PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND
 EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF
 ASCE 24.
  
 2) A9(C) = FOR EACH GARAGE SHOW THE FLOOD VENT SIZE
 CALCULATIONS FOR ENGINEERED OPENINGS SEE SECTION
 2.7.2.2 OF ASCE 24. 6. THE MINIMUM TOTAL NET AREA OF
 THE REQUIRED OPENINGS IN
 ENCLOSURE WALLS SHALL BE CALCULATED USING THE EQUATION
 - AO=0.033(1/C)(R)(AE) ---- OTHERWISE NON ENGINEERED
 OPENINGS = 1 SQ. INCH FOR EACH SQ. FOOT (SMART VENTS
 ARE ENGINEERED TO GIVE YOU 200 SQ. IN. PER VENT - YOU
 DO NOT HAVE ENOUGH VENTS IN EACH GARAGE TO MEET THE
 REQUIRED SQ. INCHES)
  
 3) B9 = SHOULD SHOW THE HIGHER OF THE 2 FLOOD
 ELEVATIONS OR BOTH (6 & 7)
  
 4) B12 = CHECK A BOX (YES OR NO)
  
 5) C2(D) = ADD AN ELEVATION (MAYBE THE LOWEST OF THE 2)
  
 6) SECTION "D" = PLEASE CHECK "CHECK HERE IF
 ATTACHMENTS" THE FLOOD VENT CERTIFICATION OR PRODUCT
 APPROVAL WOULD BE AN ATTACHMENT.
  
 7) PHOTOS = PLEASE ADD DATES TO EACH PHOTO
  
 8) PHOTOS = THE PHOTO DESCRIPTION SHOULD SAY "FRONT
 VIEW", "REAR VIEW", "LEFT SIDE VIEW" AND "RIGHT SIDE
 VIEW" (PHOTOS SHOULD BE OF THE HOUSE NOT THE SITEWALLS)
  
 9) PHOTOS = NEED TO SHOW A FLOOD VENT IN SOME OF THE
 PHOTOS.
  
 10) PLEASE PROVIDE A FINAL SURVEY.
  
 11) PLEASE PROVIDE THE FLOOD VENT CERTIFICATION - ICC
 EVALUATION REPORT OR MIAMI DADE NOA OR FLORIDA STATE
 PRODUCT APPROVAL