2022-09-30 09:05:32 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1 FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL22854-R1 |
| IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM |
| BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT CONSIDER |
| USING FL7473-R9. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL14672-R6 SYSTEM NO. W-48 DO NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -131.42 |
| FOR EXPOSURE CATEGORY D AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY D/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. |
| 3. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| WALL CONNECTIONS WILL BE IMPROVED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |