Plan Review Notes
Plan Review Notes For Permit 22081338
Permit Number 22081338
Review Stop M
Sequence Number 2
Notes
Date Text
2022-11-29 10:34:54THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOULD
 SHOW THE ENTRE HOUSE PLUS THE NEW ADDITION TO SHOW THAT
 THE EXISTING EQUIPMENT IS SIZED TO CONDITION THE
 EXISTING SPACE AND THE NEW ADDITION. THE EQUIPMENT
 SIZING CALCULATIONS SUBMITTED ARE FOR 243 SQ. FT.
 PLEASE PROVIDE THE CALCULATIONS FOR THE EXISTING PLUS
 ALL OF THE ADDITION. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER