2022-12-14 21:09:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. GROUNDING ELECTRODE SYSTEM REQUIRED TO BE |
| ESTABLISHED AT SEPARATE STRUCTURE PER NEC 250.32A. THE |
| EXCEPTION YOU ARE REFERRING TO IN 250.32A IS FOR A |
| SINGLE BRANCH CIRCUIT OR A MULTIWIRE BRANCH CIRCUIT. |
| PANEL C IS BEING FED BY A FEEDER NOT A BRANCH CIRCUIT. |
| PLEASE SEE NEC ARTICLE 100 (DEFINITIONS) FOR DIFFERENCE |
| BETWEEN "FEEDER" AND "BRANCH CIRCUIT". |
| |
| NEC 250.32A EXCEPTION READS AS FOLLOWS: A GROUNDING |
| ELECTRODE SHALL NOT BE REQUIRED |
| WHERE ONLY A SINGLE BRANCH CIRCUIT, INCLUDING A |
| MULTIWIRE |
| BRANCH CIRCUIT, SUPPLIES THE BUILDING OR STRUCTURE AND |
| THE |
| BRANCH CIRCUIT INCLUDES AN EQUIPMENT GROUNDING |
| CONDUCTOR |
| FOR GROUNDING THE NORMALLY NON-CURRENT-CARRYING METAL |
| PARTS OF EQUIPMENT. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |