2022-09-19 15:15:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 GAS COMMENTS: DENIED
  
 PER WPB FBC 107.2.1, 107.3.5.1.5, FBC FG 305.1 AND FBC
 RES G2408.1, MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL(S) FOR ALL GAS EQUIPMENT SHALL BE ON SITE AT THE
 TIME OF INSPECTION.
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR ADDITIONAL
 INFORMATION
  
  
 A. PER WPB FBC 107.2.1, 107.3.5.1 AND 107.3.5.3 (13),
 PROVIDE THE FOLLOWING.
  
 1. A GAS EQUIPMENT SCHEDULE LISTING BTU REQUIREMENTS
 FOR EACH, QUANTITIES AND TOTAL BTUS FOR THE SYSTEM.
  
 2. SPECIFY TYPE OF GAS AND SERVICE PRESSURE AT THE
 METER/REGULATOR.
  
 3. PROVIDE AND SCHEDULE AN MANUFACTURER'S OUTDOOR VENT
 KIT FOR EACH SCHEDULED TANKLESS GAS WATER HEATER.
  
 4. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE INDOOR
 GAS APPLIANCE(S) AS APPLICABLE PER FBC FG 304.1 AND FBC
 RES G2407.1.
  
 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL
 HORIZONTAL AND VERTICAL CUT SECTIONS OF PIPE PER FBC FG
 402.4.1, 402.4.2, FBC RES G2413.4.1 AND G2413.4.2.
  
 6. SPECIFY TYPE OF PIPE MATERIAL ABOVE AND BELOW GROUND
 BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING
 EHD NUMBER OF CORRUGATED STAINLESS STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE. LIST TABLES (FBC FG
 402, FBC RES G2413) FOR EACH MATERIAL USED FOR
 CALCULATIONS OF PIPE SIZES.
  
 7. SHOW COMPLIANCE WITH ELECTRICAL BONDING PER FBC FG
 310 AND FBC RES G2411.
  
 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, TO THE
 MOST REMOTE OUTLET IN THE SYSTEM PER THE FBC FG
 402.4.1, 402.4.2, 402.4.3 OR FBC RES G2413.4.1,
 G2413.4.2.
  
  
 END OF COMMENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  