2022-09-19 15:15:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| GAS COMMENTS: DENIED |
| |
| PER WPB FBC 107.2.1, 107.3.5.1.5, FBC FG 305.1 AND FBC |
| RES G2408.1, MANUFACTURER'S SPECIFICATION/INSTALLATION |
| MANUAL(S) FOR ALL GAS EQUIPMENT SHALL BE ON SITE AT THE |
| TIME OF INSPECTION. |
| |
| CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR |
| MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL |
| GAS INSPECTION. CALL 561-805-6692 FOR ADDITIONAL |
| INFORMATION |
| |
| |
| A. PER WPB FBC 107.2.1, 107.3.5.1 AND 107.3.5.3 (13), |
| PROVIDE THE FOLLOWING. |
| |
| 1. A GAS EQUIPMENT SCHEDULE LISTING BTU REQUIREMENTS |
| FOR EACH, QUANTITIES AND TOTAL BTUS FOR THE SYSTEM. |
| |
| 2. SPECIFY TYPE OF GAS AND SERVICE PRESSURE AT THE |
| METER/REGULATOR. |
| |
| 3. PROVIDE AND SCHEDULE AN MANUFACTURER'S OUTDOOR VENT |
| KIT FOR EACH SCHEDULED TANKLESS GAS WATER HEATER. |
| |
| 4. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE INDOOR |
| GAS APPLIANCE(S) AS APPLICABLE PER FBC FG 304.1 AND FBC |
| RES G2407.1. |
| |
| 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL |
| HORIZONTAL AND VERTICAL CUT SECTIONS OF PIPE PER FBC FG |
| 402.4.1, 402.4.2, FBC RES G2413.4.1 AND G2413.4.2. |
| |
| 6. SPECIFY TYPE OF PIPE MATERIAL ABOVE AND BELOW GROUND |
| BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| EHD NUMBER OF CORRUGATED STAINLESS STEEL TUBING (IF |
| APPLICABLE) FOR EACH PIPE SIZE. LIST TABLES (FBC FG |
| 402, FBC RES G2413) FOR EACH MATERIAL USED FOR |
| CALCULATIONS OF PIPE SIZES. |
| |
| 7. SHOW COMPLIANCE WITH ELECTRICAL BONDING PER FBC FG |
| 310 AND FBC RES G2411. |
| |
| 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, TO THE |
| MOST REMOTE OUTLET IN THE SYSTEM PER THE FBC FG |
| 402.4.1, 402.4.2, 402.4.3 OR FBC RES G2413.4.1, |
| G2413.4.2. |
| |
| |
| END OF COMMENTS. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| PLUMBING INSPECTOR BN2148 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| |