Plan Review Notes
Plan Review Notes For Permit 22081229
Permit Number 22081229
Review Stop B
Sequence Number 1
Notes
Date Text
2022-09-21 15:12:06PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC R 4501.17, IT APPEARS THAT THIS FENCE IS PART OF A
 POOL BARRIER. PLEASE PROVIDE ALL GATE LOCATIONS ON
 SURVEY SHOWING COMPLIANCE WITH THIS CODE SECTION
 INCLUDING:
  
 FBC R 4501.17.1.8, PLEASE SHOW GATE AND GATE LOCKING
 DEVICE DETAILS. THE GATES MUST HAVE A SELF LATCHING
 LOCKING DEVICE LOCATED NO LESS THAN 54" FROM BOTTOM OF
 GATE OR PER ALTERNATE CODE REQUIREMENTS. THE GATES MUST
 OPEN OUTWARD AWAY FROM POOL. THE GATES AND BARRIER MUST
 HAVE NO OPENING GREATER THAN 1/2" WITHIN 18" OF THE
 RELEASE MECHANISM.
  
 FBC R 45017.1.9, PLEASE SHOW ON SURVEY THE LOCATION OF
 WINDOWS AND DOORS THAT PROVIDE ACCESS TO THE POOL AREA.
 THESE OPENINGS MUST HAVE ALARMS OR ALTERNATE ALARM
 METHOD PER THIS CODE SECTION.