2022-11-21 06:20:29 | 3RD GAS REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMENDS 107.2.1 - YOU ARE STILL QUOTING THE |
| WRONG GAS CHART. THE PIPE IS PE AND THE CHART IS FOR |
| METALLIC. ALSO, IF USING THAT CHART, REGARDLESS OF |
| MATERIAL, THE BTU LOAD FOR 3/4" PIPE AT 50' (151K) IS |
| LOWER THAN THE BTU DEMAND (199K). PLEASE CHOOSE THE |
| RIGHT CHART FOR THE MATERIAL AND PRESSURE. |
| |
| 2. 2017 WPB AMENDS 107.2.1 - THE ADDRESS ON THE DRAWING |
| IS NOT CORRECT. |
| |
| 3. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS |
| REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER |
| 1. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |