Plan Review Notes For Permit 22081192 |
Permit Number |
22081192 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-10-18 10:35:03 | 2ND GAS REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE - CHANGES CREATE NEW COMMNETS - SEE #2 | | | | 2. 2020 FRC G2415.11.1 - IN CHANGING THE GAS LINE TO | | GALVANIZED (OR REMOVING THE NOTATION THAT IT IS PE), | | YOU APPEAR TO BE DRAWING THE GALVANIZED ON THE SAME | | PLANE AS THE METER INLET AND IT APPEARS THE GALVANIZED | | IS UNDERGROUNG. WITHOUT ANY OTHER NOTATIONS, I ASSUME | | IT IS UNDERGROUND. PLEASE CLARIFY. GALVANIZED PIPE IS | | NOT ALLOWED UNDERGROUND. YOUR DRAWING SHOULD ALWAYS | | LABEL THE MATERIALS AND PIPE PRESSURES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|