Plan Review Notes
Plan Review Notes For Permit 22081192
Permit Number 22081192
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-18 10:35:032ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE - CHANGES CREATE NEW COMMNETS - SEE #2
  
 2. 2020 FRC G2415.11.1 - IN CHANGING THE GAS LINE TO
 GALVANIZED (OR REMOVING THE NOTATION THAT IT IS PE),
 YOU APPEAR TO BE DRAWING THE GALVANIZED ON THE SAME
 PLANE AS THE METER INLET AND IT APPEARS THE GALVANIZED
 IS UNDERGROUNG. WITHOUT ANY OTHER NOTATIONS, I ASSUME
 IT IS UNDERGROUND. PLEASE CLARIFY. GALVANIZED PIPE IS
 NOT ALLOWED UNDERGROUND. YOUR DRAWING SHOULD ALWAYS
 LABEL THE MATERIALS AND PIPE PRESSURES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  