Plan Review Notes
Plan Review Notes For Permit 22081164
Permit Number 22081164
Review Stop B
Sequence Number 3
Notes
Date Text
2023-01-13 11:30:553RD BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE
 ROOM CREATES A SEPERATE ENCLOSED AREA (STORAGE).
  
 1. PROVIDE A STRUCTURAL DETAIL OF THE WALL BETWEEN THE
 GARAGE AND STORAGE ROOM. WALL SHALL BE DESIGNED PER
 R322.1.5 (FLOOD RESISTANT CONSTRUCTION)
 (ARCHITECTS RESPONSE-SMART FLOOD VENT INSTALLED IN
 INTERIOR WALL. FRAME WALL DETAIL PREVIOUSLY PROVIDED.)
  
 (NEW COMMENT: I HAVE REVIEWED THE CONSTRUCTION
 DOCUMENTS AND CANNOT FIND A DETAIL FOR THIS INTERIOR
 PARTITION. THE ONLY REFERENCE FOUND IS NOTE #13 ON PLAN
 PAGE A-0.00 THAT STATES ALL INTERIOR PARTITIONS TO BE
 METAL STUDS (20 GUAGE MIN) AT 16 INCH O.C. THIS DOES
 NOT COMPLY WITH THE REQUIREMENTS OF R322.
 R322.1.8FLOOD-RESISTANT MATERIALS.
 BUILDING MATERIALS AND INSTALLATION METHODS USED FOR
 FLOORING AND INTERIOR AND EXTERIOR WALLS AND WALL
 COVERINGS BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 SHALL BE FLOOD DAMAGE-RESISTANT
 MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2.
 TECHNICAL BULLITEN #2
 FLOOD DAMAGE-RESISTANT MATERIAL
 FLOOD [DAMAGE]-RESISTANT MATERIAL IS DEFINED BY THE
 NFIP AS ANY BUILDING PRODUCT [MATERIAL, COMPONENT OR
 SYSTEM] CAPABLE OF WITHSTANDING DIRECT AND PROLONGED
 CONTACT WITH FLOODWATERS WITHOUT SUSTAINING SIGNIFICANT
 DAMAGE.)
 (PLEASE DIRECT ME TO THE DETAIL "PREVIOUSLY PROVIDED"
 OR PROVIDE A STRUCTURAL DETAIL FOR THE INTERIOR
 PARTITION THAT COMPLYS WITH R322.)
  
  
 THERE ARE TWO FLOOD OPENING ON ADJACENT WALLS IN THE
 STORAGE ROOM. CORRECT.
 THE GARAGE AREA IS 998SF AND REQUIRES (5) SMART VENTS
 AT 200SF/VENT. ADD AN ADDITIONAL (2) SMART VENTS. (THIS
 IS INCORRECT. SEE BELOW:)
  
 (NEW COMMENT)
 (THE GARAGE AND THE STORAGE AREA ARE TWO SEPERATE
 AREAS)
 (UPON FURTHER REVIEW IT HAS BEEN DETERMINED THAT THE
 GARAGE IS 799SF BASED ON THE DEMENSIONS PROVIDED ON
 PLAN PAGE A-1.01.)
 (3'+9'+2'+9'+2'+9'+3')=37X21'6"=799.2SF) (3) SMART
 VENTS AT 200SF/VENT ARE REQUIRED. PROVIDED.
 (THE STORAGE AREA IS 210SF AS STATED.) (2) SMART VENTS
 ARE REQUIRED. PROVIDED.
 ELEVATION CERTIFICATE INSTRUCTIONS
 ITEM A8.A. PROVIDE THE SQUARE FOOTAGE OF THE CRAWLSPACE
 OR ENCLOSURE(S) BELOW THE LOWEST ELEVATED FLOOR OF AN
 ELEVATED BUILDING WITH OR WITHOUT PERMANENT FLOOD
 OPENINGS. TAKE THE MEASUREMENT FROM THE OUTSIDE OF THE
 CRAWLSPACE OR ENCLOSURE(S).
  
 2.
  
 3.
  
 (NEW COMMENTS)
 (THE BUILDING SQUARE FOOT DATA ON PLAN PAGE SP-1.01
 STATES PROPOSED 3 CAR GARAGE, STORAGE: 998 S.F. (LESS
 THAN 1000 S.F)
 (THE CORRECT DATA IS 3 CAR GARAGE 799 S.F. STORAGE 210
 S.F. 1009 S.F.) >1000 S.F.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  