2023-01-13 11:30:55 | 3RD BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE |
| ROOM CREATES A SEPERATE ENCLOSED AREA (STORAGE). |
| |
| 1. PROVIDE A STRUCTURAL DETAIL OF THE WALL BETWEEN THE |
| GARAGE AND STORAGE ROOM. WALL SHALL BE DESIGNED PER |
| R322.1.5 (FLOOD RESISTANT CONSTRUCTION) |
| (ARCHITECTS RESPONSE-SMART FLOOD VENT INSTALLED IN |
| INTERIOR WALL. FRAME WALL DETAIL PREVIOUSLY PROVIDED.) |
| |
| (NEW COMMENT: I HAVE REVIEWED THE CONSTRUCTION |
| DOCUMENTS AND CANNOT FIND A DETAIL FOR THIS INTERIOR |
| PARTITION. THE ONLY REFERENCE FOUND IS NOTE #13 ON PLAN |
| PAGE A-0.00 THAT STATES ALL INTERIOR PARTITIONS TO BE |
| METAL STUDS (20 GUAGE MIN) AT 16 INCH O.C. THIS DOES |
| NOT COMPLY WITH THE REQUIREMENTS OF R322. |
| R322.1.8FLOOD-RESISTANT MATERIALS. |
| BUILDING MATERIALS AND INSTALLATION METHODS USED FOR |
| FLOORING AND INTERIOR AND EXTERIOR WALLS AND WALL |
| COVERINGS BELOW THE ELEVATION REQUIRED IN SECTION |
| R322.2 OR R322.3 SHALL BE FLOOD DAMAGE-RESISTANT |
| MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2. |
| TECHNICAL BULLITEN #2 |
| FLOOD DAMAGE-RESISTANT MATERIAL |
| FLOOD [DAMAGE]-RESISTANT MATERIAL IS DEFINED BY THE |
| NFIP AS ANY BUILDING PRODUCT [MATERIAL, COMPONENT OR |
| SYSTEM] CAPABLE OF WITHSTANDING DIRECT AND PROLONGED |
| CONTACT WITH FLOODWATERS WITHOUT SUSTAINING SIGNIFICANT |
| DAMAGE.) |
| (PLEASE DIRECT ME TO THE DETAIL "PREVIOUSLY PROVIDED" |
| OR PROVIDE A STRUCTURAL DETAIL FOR THE INTERIOR |
| PARTITION THAT COMPLYS WITH R322.) |
| |
| |
| THERE ARE TWO FLOOD OPENING ON ADJACENT WALLS IN THE |
| STORAGE ROOM. CORRECT. |
| THE GARAGE AREA IS 998SF AND REQUIRES (5) SMART VENTS |
| AT 200SF/VENT. ADD AN ADDITIONAL (2) SMART VENTS. (THIS |
| IS INCORRECT. SEE BELOW:) |
| |
| (NEW COMMENT) |
| (THE GARAGE AND THE STORAGE AREA ARE TWO SEPERATE |
| AREAS) |
| (UPON FURTHER REVIEW IT HAS BEEN DETERMINED THAT THE |
| GARAGE IS 799SF BASED ON THE DEMENSIONS PROVIDED ON |
| PLAN PAGE A-1.01.) |
| (3'+9'+2'+9'+2'+9'+3')=37X21'6"=799.2SF) (3) SMART |
| VENTS AT 200SF/VENT ARE REQUIRED. PROVIDED. |
| (THE STORAGE AREA IS 210SF AS STATED.) (2) SMART VENTS |
| ARE REQUIRED. PROVIDED. |
| ELEVATION CERTIFICATE INSTRUCTIONS |
| ITEM A8.A. PROVIDE THE SQUARE FOOTAGE OF THE CRAWLSPACE |
| OR ENCLOSURE(S) BELOW THE LOWEST ELEVATED FLOOR OF AN |
| ELEVATED BUILDING WITH OR WITHOUT PERMANENT FLOOD |
| OPENINGS. TAKE THE MEASUREMENT FROM THE OUTSIDE OF THE |
| CRAWLSPACE OR ENCLOSURE(S). |
| |
| 2. |
| |
| 3. |
| |
| (NEW COMMENTS) |
| (THE BUILDING SQUARE FOOT DATA ON PLAN PAGE SP-1.01 |
| STATES PROPOSED 3 CAR GARAGE, STORAGE: 998 S.F. (LESS |
| THAN 1000 S.F) |
| (THE CORRECT DATA IS 3 CAR GARAGE 799 S.F. STORAGE 210 |
| S.F. 1009 S.F.) >1000 S.F. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |