2022-12-19 14:58:53 | 2ND BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: THE DOOR BETWEEN THE GARAGE AND THE STORAGE |
| ROOM CREATES A SEPERATE ENCLOSED AREA (STORAGE). |
| |
| 1. PROVIDE A STRUCTURAL DETAIL OF THE WALL BETWEEN THE |
| GARAGE AND STORAGE ROOM. WALL SHALL BE DESIGNED PER |
| R322.1.5 (FLOOD RESISTANT CONSTRUCTION) |
| |
| 1. THERE ARE TWO FLOOD OPENING ON ADJACENT WALLS IN THE |
| STORAGE ROOM. THE GARAGE AREA IS 998SF AND REQUIRES (5) |
| SMART VENTS AT 200SF/VENT. ADD AN ADDITIONAL (2) SMART |
| VENTS. |
| |
| R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW |
| THE DESIGN FLOOD ELEVATION SHALL: |
| 1. 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING |
| ACCESS OR STORAGE. |
| 2. 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE |
| FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH |
| SECTION R322.2.2.1: |
| |
| 2. PROVIDE THE PROPOSED SMART VENT MODEL NUMBER ON PLAN |
| PAGE A-1.01. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 3. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM |
| INSULATION. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |