2022-10-26 12:16:53 | 1ST BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA (SFHA). FLOOD ZONE AE 7. |
| SUBMIT A CONSTRUCTION DRAWING ELEVATION CERTIFICATE FOR |
| THE PROPOSED GARAGE. (SEE COMMENTS UNDER THE NFIP |
| REVIEW) |
| |
| 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| SURVEY. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE A SOILS REPORT. |
| R401.4 SOIL TESTS. |
| |
| 3. ENERGY SUBMITTAL IS MISSING THE CEILING INSULATION. |
| SHOW INSULATION TYPE AND R VALUE ON PLANS. |
| R401.2COMPLIANCE. |
| |
| 4.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE |
| ENHANCED CALCULATED DESIGN PRESSURES OF ZONES 2 AND 3. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| 5. SITE DRAINAGE PLAN C-1 SHOWS TOP OF GARAGE FLOOR TO |
| BE 6'0" NAVD. PLAN PAGE A-1.01 SHOWS TOP OF GARAGE |
| FLOOR TO BE 5'O" NAVD. |
| PLEASE CLARIFY? |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 6. PROVIDE THE LOCATION, TYPE OF VENT AND COVERAGE |
| PROVIDED FOR EACH GARAGE FLOOD VENT. |
| GARAGE IS 998 SF. |
| R322 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |