2022-12-01 09:52:00ELECTRIC REVIEW FAILED
  
 1) APPLICATION INDICATES THAT MINOR ELECTRIC WORK IS TO
 BE DONE, HOWEVER THERE IS NO ELECTRIC WORK SHOWN ON
 PLANS. IN ADDITION PLEASE PROVIDE AN ELECTRIC PLAN AND
 WORK SCOPE. FBC 107.2
 2) THE SUBMITTAL ALSO STATES THIS IS A FOR DEMOLITION.
 IF THIS IS TRUE, PLEASE REMOVE THE PROPOSED FLOOR PLAN
 FROM THE SUBMITTAL. FBC 107.2
 3) A DEMOLITION PERMIT REQUIRES AN ELECTRICAL SUB
 PERMIT APPLICATION TO BE INCLUDED WITH THE SUBMITTAL AS
 PER OUR BUILDING OFFICIALS POLICY. THIS IS A BUILDING
 DEPARTMENT POLICY TO ENSURE ELECTRICAL SAFETY DURING
 DEMOLITION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  