2023-01-06 16:27:25 | 2ND BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: VALUE HAS BEEN ADJUSTED TO $203,349.00 PER THE |
| ICC BUILDIUNG VALUATION DATA. |
| |
| COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN ADDRESSED. |
| SEE BELOW: |
| |
| 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| |
| 2. NOA 15-0406.12 (SH) EXPIRED ON 4/8/19. |
| PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA FOR |
| THE PROPOSED SH WINDOWS. |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| NOTE: NOAS DO NOT HAVE COVER SHEETS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 3.PROVIDE ROOF DRAINAGE PLAN |
| R903.4ROOF DRAINAGE. |
| UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF |
| DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE |
| ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL |
| BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |