Plan Review Notes
Plan Review Notes For Permit 22081027
Permit Number 22081027
Review Stop P
Sequence Number 2
Notes
Date Text
2022-12-09 06:59:332ND PLUMBING REVIEW
 RESPONSE LETTER FROM 1ST REVIEW NOT RECEIVED AND
 CORRECTIONS ARE NOT CLEAR. THE RE-REVIEW WAS NOT
 COMPLETED AT THIS TIME BECAUSE A RESPONSE LETTER AND/OR
 THE CORRECTIONS ARE NOT CLEAR. MAYBE A PHONE CALL OR
 EMAIL WOULD BE HELPFUL.
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. CORRECTIONS NOT CLEAR - TYPICALLY THERE IS A FLOOR
 PLAN OF THE FIXTURES WITH THE DRAINS IN THE SAME FLOOR
 PLAN. IT IS VIRTUALLY IMPOSSIBLE TO DECIPHER WHICH
 FIXTURES ARE DRAINING INTO WHICH RECEPTACLE.
 2017 WPB AMENDS 107.2.1 - THE DRAIN ISOMETRICS DO NOT
 CLEARLY INDICATE WHICH FIXTURES DISCHARGE TO WHICH
 DRAINS. PLEASE SHOW A FLOOR PLAN FOR THE DRAINS THAT
 CLEARLY SHOW THE LOCATION OF EACH FIXTURE'S DISCHARGE
 TO CLARIFY WHICH ONES ARE INTO THE SANITARY AND WHICH
 ARE INTO THE GREASE WASTE. SEE COMMENT #2
  
 2. IT APPEARS THIS COMMENT WAS NOT FULLY ADDRESSED, BUT
 CANNOT BE VERIFIED UNTIL COMMENT #1 IS ADDRESSED. IS
 THE EYE WASH STILL GOING INTO THE GREASE WASTE?
 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK,
 DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES
 THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE
 GOING TO THE SANITARY AND NOT TO THE GREASE WASTE.
 PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF
 GREASE WASTE AND SANITARY WASTE. CURRENLY, AT THE VERY
 LEAST, THE HAND SINK IS GOING TO THE GREASE WASTE AND
 SHOULD NOT.
  
 3. 2017 WPB AMENDS 107.2.1 - IT APPEARS THAT ALL THE
 DRAINS ARE LABELED AS FLOOR DRAINS. INDIRECT WASTES
 SHOULD DISCHARGE TO FLOOR SINKS OR HUB DRAINS AND FLOOR
 DRAINS RECEIVE FLOOR DRAINAGE. PLEASE CORRECTLY LABEL
 AND DETAIL THE FLOOR SINKS AND FLOOR DRAINS.
  
 4. NOT ADDRESSED. THE ISOMETRIC AND THE PIPING DIAGRAM
 7-P501 DOES NOT SHOW A THERMOSTATIC MIXING DEVICE AT
 THE WATER HEATER
 HOT WATER 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS
 - THE THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE
 THE LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE
 PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE
 OF HOT WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, SHALL BE INSTALLED AT THE HOT WATER
 SOURCE PER 613.1.
  
 5. NOT ADDRESSED. A DETAIL SHOWING MIXING VALVES AT THE
 PUBLIC HANDWASHING SINKS NOT SHOWN.
 TEMPERED WATER/PUBLIC HAND WASHING 2020 FPC
 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR THE LIMITING
 DEVICE REQUIRED FOR PUBLIC HANDWASHING FACILITIES AND
 TEMPERED WATER. THE DEVICE SHOULD CONFORM TO ASSE 1070.
  
 6. 16-P501 STILL DOES NOT DETAIL THE REQUIRED OIL ALARM
 FOR THE ELEVATOR SUMP.
 2020 FPC 1003.4 - PLEASE DETAIL THE OIL ALARM FOR THE
 ELEVATOR SUMPS OR SHOW THE OIL SEPARATOR THAT WOULD BE
 REQUIRED IN IT'S ABSENCE.
  
 7. -------THE ELEVATOR SUMP PUMP DISCHARGE CANNOT GO TO
 THE STORM.
 WPB ORD. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
  (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE
 OR ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORM WATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE.
  
  
 8. -------THE DISCHARGE FROM AIR HANDLERS/AIR
 CONDITIONING CONDENSATE CANNOT DISCHARGE INTO THE
 SANITARY. IT MUST GO TO THE STORM OR OTHER APPROVED
 PLACE OF DISPOSAL.
 WPB ORD. SEC. 90 - 126 - PROHIBITIONS AND LIMITATIONS
 OF DISCHARGE.
  A) GENERALLY. USERS SHALL NOT DISCHARGE POLLUTANTS
 INTO THE WWF UNLESS IN ACCORDANCE WITH THIS ARTICLE.
  (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE
 INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE
 PASS THROUGH OR INTERFERE WITH THE OPERATION OR
 PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO
 THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER
 CONTAINING ANY OF THE FOLLOWING:
  (5) STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  