Plan Review Notes For Permit 22081027 |
Permit Number |
22081027 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-12-16 14:00:30 | 2ND REVIEW FMC | | PERMIT: 22081027 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE RESPOND TO 1ST CYCLE COMMENT 5 BELOW: | | 5)SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS | | EXHAUST SYSTEM. FMC TABLE 403.3.1.1 | | | | 2) SHEET M601: VENTILATION SCHEDULE- RTU-5 ??? PLEASE | | PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE RTU-5 | | BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANCY | | DENSITY FROM TABLE 403.3.1.1. SOME OF THE OCCUPANT | | COUNTS APPEAR TO BE LOW IN THE VENTILATION SCHEDULE | | BASED ON TABLE 403.3.1.1, WHICH MAKES THE REQUIRED | | OUTDOOR AIR FOR THAT AREA TO BE LOW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|