Plan Review Notes
Plan Review Notes For Permit 22081027
Permit Number 22081027
Review Stop M
Sequence Number 2
Notes
Date Text
2022-12-16 14:00:302ND REVIEW FMC
 PERMIT: 22081027
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE RESPOND TO 1ST CYCLE COMMENT 5 BELOW:
 5)SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS
 EXHAUST SYSTEM. FMC TABLE 403.3.1.1
  
 2) SHEET M601: VENTILATION SCHEDULE- RTU-5 ??? PLEASE
 PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE RTU-5
 BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANCY
 DENSITY FROM TABLE 403.3.1.1. SOME OF THE OCCUPANT
 COUNTS APPEAR TO BE LOW IN THE VENTILATION SCHEDULE
 BASED ON TABLE 403.3.1.1, WHICH MAKES THE REQUIRED
 OUTDOOR AIR FOR THAT AREA TO BE LOW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  