2022-12-09 15:10:51TARGET REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING AD110 SHOWS THE REMOVAL OF 2 EXIT DOORS FOR
 EXIT NUMBER 4 - DRAWING A020 SHOWS THE DOORS REPLACED
 WITH A WALL - DRAWING A021 SAYS THAT THE EXIT CONSIST
 OF 1 - 8' EXIT AND 1 - 3' EXIT PLEASE RE EVALUATE THE
 MEANS OF EGRESS - FBC 1005.4 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
  
 2) DRAWING ACC2 - ALL ACCESSIBLE PARKING SPACES NEED TO
 BE 12' WIDE - FBC 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM)
 WIDE,
  
 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS AS TO THE WALL
 FINISH AND CEILING FINISH FIRE CLASSIFICATIONS PER FBC
 803.1
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OF RECORD FBC WPB 107.3.4
  
 5) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
  
  
  
  