2022-10-06 13:22:17 | 1ST PLUMBING REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMENDS 107.2.1 - THE DRAIN ISOMETRICS DO |
| NOT CLEARLY INDICATE WHICH FIXTURES DISCHARGE TO WHICH |
| DRAINS. PLEASE SHOW A FLOOR PLAN FOR THE DRAINS THAT |
| CLEARLY SHOW THE LOCATION OF EACH FIXTURE'S DISCHARGE |
| TO CLARIFY WHICH ONES ARE INTO THE SANITARY AND WHICH |
| ARE INTO THE GREASE WASTE. SEE COMMENT #2 |
| |
| 2. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK, |
| DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES |
| THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE |
| GOING TO THE SANITARY AND NOT TO THE GREASE WASTE. |
| PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF |
| GREASE WASTE AND SANITARY WASTE. CURRENLY, AT THE VERY |
| LEAST, THE HAND SINK IS GOING TO THE GREASE WASTE AND |
| SHOULD NOT. |
| |
| 3. 2017 WPB AMENDS 107.2.1 - IT APPEARS THAT ALL THE |
| DRAINS ARE LABELED AS FLOOR DRAINS. INDIRECT WASTES |
| SHOULD DISCHARGE TO FLOOR SINKS OR HUB DRAINS AND FLOOR |
| DRAINS RECEIVE FLOOR DRAINAGE. PLEASE CORRECTLY LABEL |
| AND DETAIL THE FLOOR SINKS AND FLOOR DRAINS. |
| |
| 4. HOT WATER 2020 FPC - 607.1.1 TEMPERATURE LIMITING |
| MEANS - THE THERMOSTAT CONTROL ON THE WATER HEATER |
| CANNOT BE THE LIMITING DEVICE FOR HOT WATER DELIVERY. |
| PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE |
| PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN |
| ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR |
| PUBLIC HANDWASHING 607.1.2/419.5. AND, SHALL BE |
| INSTALLED AT THE HOT WATER SOURCE PER 613.1. |
| |
| 5. TEMPERED WATER/PUBLIC HAND WASHING 2020 FPC |
| 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR THE LIMITING |
| DEVICE REQUIRED FOR PUBLIC HANDWASHING FACILITIES AND |
| TEMPERED WATER. THE DEVICE SHOULD CONFORM TO ASSE 1070. |
| |
| 6. 2020 FPC 1003.4 - PLEASE DETAIL THE OIL ALARM FOR |
| THE ELEVATOR SUMPS OR SHOW THE OIL SEPARATOR THAT WOULD |
| BE REQUIRED IN IT'S ABSENCE. |
| |
| 7. -------THE ELEVATOR SUMP PUMP DISCHARGE CANNOT GO TO |
| THE STORM. |
| WPB ORD. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT |
| CONNECTIONS. |
| (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE |
| OR ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE |
| STORM WATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN |
| VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS |
| RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE |
| PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR |
| OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS |
| OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE |
| CONNECTION WAS MADE. |
| |
| |
| 8. -------THE DISCHARGE FROM AIR HANDLERS/AIR |
| CONDITIONING CONDENSATE CANNOT DISCHARGE INTO THE |
| SANITARY. IT MUST GO TO THE STORM OR OTHER APPROVED |
| PLACE OF DISPOSAL. |
| WPB ORD. SEC. 90 - 126 - PROHIBITIONS AND LIMITATIONS |
| OF DISCHARGE. |
| A) GENERALLY. USERS SHALL NOT DISCHARGE POLLUTANTS |
| INTO THE WWF UNLESS IN ACCORDANCE WITH THIS ARTICLE. |
| (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE |
| INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE |
| PASS THROUGH OR INTERFERE WITH THE OPERATION OR |
| PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO |
| THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER |
| CONTAINING ANY OF THE FOLLOWING: |
| (5) STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN |
| WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING |
| POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| IN WRITING. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |