2022-10-13 11:04:18 | 1ST REVIEW FMC |
| PERMIT: 22081027 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE ENERGY CALCULATIONS AND THE |
| MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON THE |
| 2020 FLORIDA ENERGY CODE. |
| |
| 2) PLEASE ADD A NOTE ON THE REFRIGERATION DRAWINGS |
| STATING THAT ALL REFRIGERATION WILL REQUIRE A SEPARATE |
| PERMIT APPLICATION, SUBMITTAL AND REVIEW AS IT WILL NOT |
| BE REVIEWED UNDER THIS PERMIT APPLICATION. THEY WILL |
| ALSO BE REQUIRED TO MEET- FEC C403.2.14 REFRIGERATION |
| EQUIPMENT PERFORMANCE. |
| REFRIGERATION EQUIPMENT PERFORMANCE SHALL BE DETERMINED |
| IN ACCORDANCE WITH SECTIONS C403.2.14.1 AND C403.2.14.2 |
| FOR COMMERCIAL REFRIGERATORS, FREEZERS, |
| REFRIGERATOR-FREEZERS, WALK-IN COOLERS, WALK-IN |
| FREEZERS AND REFRIGERATION EQUIPMENT. THE ENERGY USE |
| SHALL BE VERIFIED THROUGH CERTIFICATION UNDER AN |
| APPROVED CERTIFICATION PROGRAM OR, WHERE |
| A CERTIFICATION PROGRAM DOES NOT EXIST, THE ENERGY USE |
| SHALL BE SUPPORTED BY DATA FURNISHED BY THE EQUIPMENT |
| MANUFACTURER. |
| EXCEPTION: |
| WALK-IN COOLERS AND WALK-IN FREEZERS REGULATED UNDER |
| FEDERAL LAW IN ACCORDANCE WITH SUBPART R OF 10 CFR 431. |
| |
| 3) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR |
| ALL NEW MECHANICAL UNITS. FEC C403.2.1 |
| |
| 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF |
| SPACE FOR THIS PROJECT. PLEASE USE THE OCCUPANCY |
| CLASSIFICATIONS LISTED IN TABLE 403.3.1.1 WHEN NAMING |
| EACH SPACE. FMC 403.3.1.1 |
| |
| 5) SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS |
| EXHAUST SYSTEM. FMC TABLE 403.3.1.1 |
| |
| |
| 6) SHEET M311: THERE ARE 3 CU???S SHOWN ON THE DRAWING |
| FOR AC-3, AC-4 AND AC-5. ARE THESE NEW CU???S GOING TO |
| BE MOUNTED ON THE ROOF? IF SO PLEASE SHOW THE ANCHORAGE |
| DETAILS. FBC 107.3.5 |
| |
| 7) PLEASE SHOW A MECHANICAL ROOF DRAWING SHOWING THE |
| EXISTING AND NEW SYSTEMS AND THE DISTANCE FROM THE |
| ROOFS EDGE. FMC 304.11 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |