2022-10-13 11:04:181ST REVIEW FMC
 PERMIT: 22081027
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS AND THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS BASED ON THE
 2020 FLORIDA ENERGY CODE.
  
 2) PLEASE ADD A NOTE ON THE REFRIGERATION DRAWINGS
 STATING THAT ALL REFRIGERATION WILL REQUIRE A SEPARATE
 PERMIT APPLICATION, SUBMITTAL AND REVIEW AS IT WILL NOT
 BE REVIEWED UNDER THIS PERMIT APPLICATION. THEY WILL
 ALSO BE REQUIRED TO MEET- FEC C403.2.14 REFRIGERATION
 EQUIPMENT PERFORMANCE.
 REFRIGERATION EQUIPMENT PERFORMANCE SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTIONS C403.2.14.1 AND C403.2.14.2
 FOR COMMERCIAL REFRIGERATORS, FREEZERS,
 REFRIGERATOR-FREEZERS, WALK-IN COOLERS, WALK-IN
 FREEZERS AND REFRIGERATION EQUIPMENT. THE ENERGY USE
 SHALL BE VERIFIED THROUGH CERTIFICATION UNDER AN
 APPROVED CERTIFICATION PROGRAM OR, WHERE
 A CERTIFICATION PROGRAM DOES NOT EXIST, THE ENERGY USE
 SHALL BE SUPPORTED BY DATA FURNISHED BY THE EQUIPMENT
 MANUFACTURER.
 EXCEPTION:
 WALK-IN COOLERS AND WALK-IN FREEZERS REGULATED UNDER
 FEDERAL LAW IN ACCORDANCE WITH SUBPART R OF 10 CFR 431.
  
 3) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR
 ALL NEW MECHANICAL UNITS. FEC C403.2.1
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE FOR THIS PROJECT. PLEASE USE THE OCCUPANCY
 CLASSIFICATIONS LISTED IN TABLE 403.3.1.1 WHEN NAMING
 EACH SPACE. FMC 403.3.1.1
  
 5) SHEET M351: PLEASE SHOW THE FITTING/DRESSING ROOMS
 EXHAUST SYSTEM. FMC TABLE 403.3.1.1
  
  
 6) SHEET M311: THERE ARE 3 CU???S SHOWN ON THE DRAWING
 FOR AC-3, AC-4 AND AC-5. ARE THESE NEW CU???S GOING TO
 BE MOUNTED ON THE ROOF? IF SO PLEASE SHOW THE ANCHORAGE
 DETAILS. FBC 107.3.5
  
 7) PLEASE SHOW A MECHANICAL ROOF DRAWING SHOWING THE
 EXISTING AND NEW SYSTEMS AND THE DISTANCE FROM THE
 ROOFS EDGE. FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  