2022-08-23 06:45:49 | | | | | 1. 2017 WPB AMEND - 107.3.5 - THE SPEC SHEET FOR THE | | BACKFLOW DEVICE NEEDS TO INDICATE IT IS LEAD FREE AND | | USC APPROVED. BE SURE TO HIGHLIGHT THE MAKE, MODEL, AND | | SIZE OF THE DEVICE. OF THE TWO SPEC'D, ONE IS NOT LEAD | | FREE. | | | | 2. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE A BASIC | | SITE PLAN SHOWING THE LOCATION OF THE BACKFLOW | | PREVENTER | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|