Plan Review Notes
Plan Review Notes For Permit 22080966
Permit Number 22080966
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-23 06:49:12 
  
 1. 2017 WPB AMEND - 107.3.5 - THE SPEC SHEET FOR THE
 BACKFLOW DEVICE NEEDS TO INDICATE IT IS LEAD FREE AND
 USC APPROVED. BE SURE TO HIGHLIGHT THE MAKE, MODEL, AND
 SIZE OF THE DEVICE. OF THE TWO SPEC'D, ONE IS NOT LEAD
 FREE.
  
 2. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE A BASIC
 SITE PLAN SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER
  