2022-12-21 14:54:02 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT # 22080961 |
| 606 59TH ST. |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. |
| |
| ***IMPORTANT |
| CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| BEFORE PERMIT ISSUANCE. |
| |
| 1-LOT DRAINAGE PROVISO: |
| CONTRACTOR TO COORDINATE WITH RETAINING WALL PERMIT |
| #22120731. |
| |
| 2- ENERGY CALCULATIONS: |
| A)OK. |
| B)OK. |
| C)OK. |
| D)OK. |
| |
| PREVIOUS COMMENT: |
| E)ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL |
| ROOMS AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION. |
| ALSO, NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW |
| COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION. |
| NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON |
| ROOM SIZE. |
| |
| RESPONSE TO REVISED PLAN E-1 UPLOADED ON 12/20/22: |
| REVISED ELECTRICAL PLAN IS MISSING THE LIVING ROOM |
| CEILING FAN AND SIZE. |
| ALSO, MASTER BEDROOM AND STUDY ROOM SPECIFIED CEILING |
| FAN SIZE DOESN'T COMPLY WITH TABLE R405.7.6 FBC-ENERGY |
| CONSERVATION. REVISE PLAN AS REQUIRED. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |