2022-12-13 13:34:04 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT # 22080961 |
| 606 59TH ST. |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. |
| |
| ***IMPORTANT |
| CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| BEFORE PERMIT ISSUANCE. |
| |
| ***IMPORTANT |
| CONTRACTOR TO SUBMIT PERMIT APPLICATION AND DETAILS AND |
| SURVEY FOR DRAINAGE RETAINING WALL TO ALLOW FOR |
| BUILDING PROVISO. |
| |
| |
| ORIGINAL COMMENT: |
| 1-LOT DRAINAGE |
| PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE |
| IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT |
| PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE |
| WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY |
| AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| RESPONSE: |
| PROPOSED DRAINAGE PLAN SPECIFIES A RETAINING WALL ON |
| THE WEST SIDE. A SEPARATE PERMIT IS REQUIRED FOR THE |
| CONSTRUCTION OF THIS WALL. PROVIDE COMPLETE STRUCTURAL |
| DETAILS/SPECIFICATIONS UNDER A SEPARATE PERMIT. SEC. |
| R301.1 FBC-RESIDENTIAL. SEC. 105.1 CITY AMENDMENTS. |
| |
| 2- ENERGY CALCULATIONS: |
| A)OK. |
| B)OK. |
| C)OK. |
| D)OK. |
| |
| ORIGINAL COMMENT: |
| E)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT. |
| PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS. |
| REVISE AS REQUIRED OR ENGINEER OF RECORD TO REVISE |
| PLANS SHOWING COMPLIANCE WITH THIS SECTION. SEC. |
| R405.7.6 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| ELECTRICAL PLAN DOESN'T SHOW CEILING FANS ON ALL ROOMS |
| AS REQUIRED BY R405.7.6 FBC-ENERGY CONSERVATION. ALSO, |
| NEED TO SPECIFY ALL THE CEILING FAN SIZES TO SHOW |
| COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION. |
| NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON |
| ROOM SIZE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |