Plan Review Notes For Permit 22080953 |
Permit Number |
22080953 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-11-08 13:40:02 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-5.2 PLEASE SHOW THE GRAB BAR DETAILS FOR | | THE ADDED SHOWER PER FBC A 213.2 TOILET ROOMS AND | | BATHING ROOMS. WHERE BATHING ROOMS ARE PROVIDED, EACH | | BATHING ROOM SHALL COMPLY WITH 603. | | | | 2) GRAB BAR HEIGHT SHOWN ON DRAWING A-5.2 MAXIMUM | | HEIGHT SHOULD BE TO THE TOP OF THE GRIPPING SURFACE PER | | FBC A 609.4POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, |
|