2022-08-30 15:32:32 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22080953 |
| 8/30/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P-2.0A: SUBMIT ENLARGED AND DIMENSIONED |
| ARCHITECTURAL PLANS AND DETAILS FOR THE NEW OFFICE |
| BATHROOM SHOWING COMPLIANCE WITH THE FBC ACC WHERE |
| REQUIRED- SEC. 213.1 FBC ACC, & SECS. 107.2.1 & |
| 107.3.5.1.3 WPB. DETAILS REQUIRED- |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SEC. 606.2. |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALLS- |
| SEC. 604.2. |
| E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR- SECTION 604.4 (SEE EXCEPTION 1). |
| F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- SEC. 606.3 (SEE EXCEPTION 1). |
| G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE |
| REFLECTIVE SURFACE- SEC. 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4. (SEE |
| EXCEPTION 1). |
| I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| 606.2 (SEE EXCEPTION 2). |
| L) SHOWER WIDTH AND DEPTH DIMENSIONS- SEC. 608.2.2 |
| M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| SHOWER- SECTION 608.2.2.1 |
| N) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3.2. (SEE SEC. |
| 608.3 EXCEPTION 1). |
| O) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| SHOWER- SEC. 608.5.2. |
| |
| 2) P-2.0A: PROVIDE A SHOWER PAN DETAIL- SEC. 421.5.2 |
| FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |