2022-09-01 07:11:00 | 1ST REVIEW FMC |
| PERMIT: 22080953 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) MEP NARRATIVE LISTS SHEET M-2.1A, THERE IS NO SUCH |
| SHEET SUBMITTED IN THIS SUBMITTAL. |
| |
| 2) SHEET M-2.1B: THERE IS A NEW 2 INCH VENT PIPE FOR |
| TANK ON THIS REVISED DRAWING BUT NOTHING TO EXPLAIN |
| WHAT IT IS FOR. PROVIDE AN EXPLANATION. FBC 107.3.5 |
| |
| 3) SHEET M-2.1B: EXPLAIN NOTE 15. FBC 107.3.5 |
| |
| 4) SHEET M-4.2 WAS SUBMITTED BUT NO NARRATIVE WAS |
| SUBMITTED EXPLAINING THE CHANGES. PLEASE SUBMIT A |
| NARRATIVE FOR THIS SHEET. |
| |
| 5) SHEET M-5.2: IT APPEARS THAT A NEW ROOM WAS ADDED. |
| PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL |
| EQUIPMENT SIZING CALCULATIONS ALONG WITH THE EQUIPMENT |
| SCHEDULE FOR THIS NEW ROOM. FBC 107.3.5 |
| |
| 6) SHEET M-5.2: THE DOTTED AREA AT THE BOTTOM LEFT OF |
| THE DRAWING INDICATES TO REFER TO SHEET M-2.2A AND |
| M-5.3 FOR HVAC LAYOUT IN THIS AREA. NEITHER SHEET HAS |
| THIS DETAIL. PLEASE SHOW WHICH DRAWING SHOWS THIS |
| INFORMATION. FBC 107.3.5 |
| |
| 7) SHEET M-7.1: IN THE COMMON AREA SPLIT SYSTEM |
| SCHEDULE THE NEW AHU-7 IS LISTED FOR AN OFFICE, THIS |
| NEW UNIT IS FOR THE NEW ROOM THAT IS LISTED ON SHEET |
| M-5.2 AS PART OF THE CLUB HOUSE SEATING AREA. PROVIDE |
| ACCURATE INFORMATION ABOUT THIS NEW UNIT. FBC 107.3.5 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |