Plan Review Notes For Permit 22080886 |
Permit Number |
22080886 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-03-17 10:27:52 | 3RD PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC P3101.2.1 - THE BATHROOM GROUPS AND THE | | KITCHEN ARE NOT VENTED. THE DOUBLE BOWL LAV IN THE | | MASTER HAS A TRAP BELOW THE FLOOR THAT SERVES TWO | | FIXTURES AND CANNOT, AND IT'S NOT VENTED. SHOWING TRAPS | | BENEATH THE FLOOR FOR EACH LAVATORY IS BOTH NOT TYPICAL | | AND NOT TO CODE. THE RISER ON EACH TRAP IS LIMITED TO | | 24" (FRC P3201.6), AND THE CABINET HEIGHT COMBINED | | WOULD EXCEED THAT. ALSO, WOULD CREATE AN ILLEGAL TRAP | | TYPE (S-TRAP) PLEASE SUBMIT A CODE COMPLIANT DRAWING. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | |
|