Plan Review Notes
Plan Review Notes For Permit 22080886
Permit Number 22080886
Review Stop M
Sequence Number 3
Notes
Date Text
2023-03-16 08:20:283RD REVIEW FMC
 PERMIT: 22080886
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FIRST FLOOR BATH EXHAUST FAN SHOULD BE A MINIMUM OF
 50 CFM. FRC TABLE M1506.2
  
 2) PROVIDE THE DUCT SIZES FOR ALL BATH EXHAUST FANS.
 FRC TABLE M1506.2
  
 3) THE RETURNS DO NOT SHOW ANY DUCTWORK. IS THE SPACE
 ABOVE THE CEILING TO BE A RETURN AIR PLENUM? IF SO, ADD
 A DETAIL DRAWING AND PROVIDE A NOTE ON THE DRAWINGS TO
 SHOW THIS OR SHOW THE RETURN AIR DUCTWORK SYSTEM. FRC
 M1601.1.1 NOTE 7.4
  
 4) PROVIDE THE DRYER DUCT MATERIAL, LENGTH, AND
 TERMINATION LOCATION. FRC M1502
  
 5) PROVIDE THE ANCHORAGE DETAIL FOR THE CONDENSING
 UNIT. FRC M1307.2
  
 6) PROVIDE THE CONDENSATE DISPOSAL PIPING AND
 TERMINATION LOCATION. FRC M1411.3
  
 7) PROVIDE THE TERMINATION LOCATION FOR THE KITCHEN
 HOOD EXHAUST. FRC M1506.3
  
 8) THE DESIGNER OF THE MECHANICAL SYSTEM WILL NEED TO
 DIGITALLY SIGN THE DOCUMENTS. FS 471/481
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  