Plan Review Notes For Permit 22080886 |
Permit Number |
22080886 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-01-31 07:44:31 | 2ND REVIEW FMC | | PERMIT: 22080886 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-1 IS THE ELECTRICAL DRAWING. PROVIDE A | | COMPLETE MECHANICAL DRAWING FOR THIS PROJECT ALONG WITH | | THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT | | SIZING CALCULATIONS. | | SEE BELOW: | | | | PROVIDE ALL THAT APPLY FROM THE LIST BELOW: | | | | FBC 107.3.5- | | MECHANICAL: | | 1. ENERGY CALCULATIONS | | 2. EXHAUST SYSTEMS: | | CLOTHES DRYER EXHAUST | | KITCHEN EQUIPMENT EXHAUST | | SPECIALTY EXHAUST SYSTEMS | | 3. EQUIPMENT | | 4. EQUIPMENT LOCATION | | 5. MAKE-UP AIR | | 6. ROOF-MOUNTED EQUIPMENT | | 7. DUCT SYSTEMS | | 8. VENTILATION | | 9. COMBUSTION AIR | | 10. CHIMNEYS, FIREPLACES AND VENTS | | 11. APPLIANCES | | 12. BOILERS | | 13. REFRIGERATION | | 14. BATHROOM VENTILATION | | 15. LABORATORY | | 16. DESIGN FLOOD ELEVATION | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|