2022-10-17 15:00:18 | ELECTRICAL REVIEW FAILED |
| |
| 1) ELECTRIC PANELS APPEAR TO BE LOCATED IN A CLOSET |
| WHICH IS NON-COMPLIANT WITH NEC 240.24(D) |
| 2) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE |
| DISCONNECTS AND METERS. FBC 107.2 |
| 3) RISER DIAGRAM DETAILS ELECTRIC PANEL WITH #3 CU |
| FEEDERS SUPPLING A 200 AMP PANEL NOT IN COMPLIANCE WITH |
| NEC 310.15. PLEASE CORRECT AND SIZE FEEDERS AS PER |
| 310.15 TABLES |
| 4) PLEASE INCLUDE A NOTE WITH DRAWINGS STATING |
| GENERATORS, POOL AND SITE LIGHTING ARE UNDER SEPARATE |
| PERMITS |
| 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AT REAR OF |
| HOUSE AND NEXT TO AC EQUIPMENT AS PER NEC 210.50 (E), |
| 210.63 AND 210.64 |
| 6) IT APPEARS RECEPTACLE SPACING IN TO LEFT OF SINK IN |
| KITCHEN IS NOT COMPLIANT WITH NEC 210.52 FOR RECEPTACLE |
| SPACING |
| 7) PLEASE DETAIL DISHWASHER AND CLOTHES WASHER |
| RECEPTACLES ON ELECTRIC FLOOR PLAN. FBC 107.2 |
| 8) ELECTRIC PANEL SIZE ON RISER DIAGRAM CONFLICTS WITH |
| SIZE ON PANEL SCHEDULE. PLEASE CORRECT AS APPLICABLE. |
| FBC 107.2 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |